Has The Fire Marshal, Osha Inspector or Your Insurance Company Inspector Visited You Lately?See The Requirement Reference Exit Signs & Emergency Lights
Emergency Lighting | Monthly | Quarterly | Semi-annual | Annual | CODE | NFPA 101 |
| | Testing |  | | | | 7-9.3 | A functional test shall be conducted on every required emergency lighting system at 30-day intervals for not less than 30 seconds. |
| | Annual Test | | | |  | 7-9.3 | An annual test shall be conducted on every required battery-powered emergency lighting system for not less than 11/2 hours. Equipment shall be fully operational for the duration of the test. |
| | Exit Signs/Lighting | Monthly | Quarterly | Semi-annual | Annual | CODE | NFPA 101 |
| | Visual Inspection |  | | | | 7-10.9.1 | Exit signs shall be visually inspected for operation of the illumination sources at intervals not to exceed 30 days. |
| | Annual Test | | | |  | 7-10.9.2 | Exit signs connected to or provided with a battery-operated emergency illumination source, where required in 7.10.4, shall be tested and maintained in accordance with 7.9.3. |