Emergency Lighting

Monthly

Quarterly

Semi-annual

 Annual

CODENFPA 101
 Testing   7-9.3A functional test shall be conducted on every required emergency lighting system at 30-day intervals for not less than 30 seconds.
 Annual Test   7-9.3An annual test shall be conducted on every required battery-powered emergency lighting system for not less than 11/2 hours. Equipment shall be fully operational for the duration of the test. 
 

Exit Signs/Lighting

Monthly

Quarterly

Semi-annual

 Annual

CODENFPA 101
 Visual Inspection   7-10.9.1Exit signs shall be visually inspected for operation of the illumination sources at intervals not to exceed 30 days.
 Annual Test   7-10.9.2Exit signs connected to or provided with a battery-operated emergency illumination source, where required in 7.10.4, shall be tested and maintained in accordance with 7.9.3.